AM series protection relay are applicable to the user substation which the input voltage is 35kv and below. We adopt mature technology solutions to ensure the quality of the AM relay. The AM relay are widely used in substations, subsection posts and ring main units for office buildings, commercial buildings, communication buildings, mine buildings and so on.
Rated Parameter | Power Supply | Power supply: AC/DC220V, Or AC/DC110V, oR DC48V(Reference the wiring diagram) |
Range: Power supply x (1±20%) | ||
Maximum power consumption:≤10W(DC) | ||
Rated Voltage | Rated Voltage: AC100V | |
Range: 1-120V | ||
Accuracy: ±0.5% | ||
Power Consumption: ≤0.5VA(Single phase) | ||
Overload capacity: 1.2 times rated voltage for continous work;2 times for 10 seconds | ||
Rated Current | Rated current: AC 5A/1A(See the device wiring diagram) | |
Range:0.04In~15In | ||
Power consumption:≤0.5VA(Single phase) | ||
Over capacity:2 times rated current for continuous work;40 times for 1 second | ||
Frequency | Rated frequency:50Hz or 60 Hz | |
Range:45~55Hz | ||
Accuracy:±0.1Hz | ||
Digital Inut | Rated Voltage: AC/DC220V, AC/DC110V, DC48V(Similar to power supply) | |
Voltage Range: Rated voltage x (1±20%) | ||
Power Consumption:≤1W(DC220V)(Single channel) | ||
Digital Output | Mechanical life: ≥10000 times | |
Switching capacity: ≥1000W, L/R=40ms | ||
On current: continuous≥5A short time(200ms)≥30A | ||
Interrupting capacity: ≥30W,L/R=40ms | ||
Normal Working Conditions | Ambient temperature: -10℃~+55℃ | |
Device storage, transport allows the ambient temperature is -25℃~+70℃ | ||
Relative humidity: 5%~95%(The product does | ||
Altitude: ≤4000m |
A complete set of protection, related to the application
4 current input, 4 voltage input, 12DI, 5DO
Auxiliary power supply adapts with AC220V, DC220V, DC110V, AC110V
1 RS485 serial communication, IEC60870-5-103 and Modbus-RTU
1 RS232 for user update
1 GPS for GPS timing
More than 200 sequence of event records, more than 400 system logs, and more than 10 seconds tripping context records
Powerful graphic programmable Logic
Any IoT energy management system problem pls contact us, our experts will reply you within 24 hours.
Tel:
+86-18761599716
E-mail:
Address:
No.5 Dongmeng Road, Nanzha Street, Jiangyin City, Jiangsu Province, China.