AMC100 series AC precision power distribution monitoring device is a measuring device designed specifically for power management of data center servers. The device is compact in design and can monitor the full electrical parameters, input and output switches and the status of the lightning arrester of A+B two incoming lines and 192 outgoing lines in real time.
Instrument model | AMC100-FAK30 | AMC100-FAK48 | |
Measurement parameters | Voltage, current, frequency, active power, reactive power, power factor, active energy, reactive energy, 2-31 times total current harmonic content | ||
Bus voltage | Rated | 220VAC | |
Measuring range | ±20% | ||
Overload | Instantaneous voltage 2 times/sec | ||
Current outlet loop | Rated | 50mA | |
Range | 0.125~60mA | ||
Overload | Continuous 1.2 times, instantaneous 10 times/sec | ||
Input frequency | AC45~65Hz | ||
Measure | Outlet | Voltage/current/active power/active energy level 0.5, reactive power/reactive energy level 1 | |
Auxiliary power | Powered by AMC100-ZA; DC 12-24V when used alone | ||
Environment | Temperature | Work: -15℃~55℃ Storage: -25℃~70℃ | |
Humidity | Relative humidity≤93% | ||
elevation | ≤2500m | ||
Communication | RS485/Modbus-RTU | ||
Installation Method | DIN35mm rail or bottom plate installation | ||
Protection level | IP20 | ||
Pollution level | 2 | ||
Security | Insulation | The insulation resistance between all terminals and the conductive parts of the shell is not less than 100MΩ | |
Withstand voltage | The voltage and current signals of circuit A//the voltage and current signals of circuit B//other ports meet AC2kV for 1min, the leakage current should be less than 2mA, and there is no breakdown or flashover. | ||
Electromagnetic compatibility | Anti-static interference | Level 4 | |
Resistance to radio frequency electromagnetic field radiation | Level 3 |
Designed specifically for the power supply management of server in the data center
A+B independent 15 circuits(30 in total)
U, I, P, Q, S, PF, kWh, kvarh
2nd-31st Harmonic
kWh Class 0.5
DIN 35 mm