ARD3T motor protector (hereinafter referred to as the protector) is suitable for low-voltage motor circuits with rated voltage up to 380V and integrates protection, measurement, control, communication, operation and maintenance.Its perfect protection function ensures the safe operation of the motor, with logic programmable function, can meet a variety of control methods.
Its perfect protection function ensures the safe operation of the motor, with logic programmable function, can meet a variety of control methods.
Protective function
Control function
Measurement, monitoring
SOE
Communication
RS485 Modbus RTU or Profibus-DP
Technical parameters | Technical indicators | |
Protector auxiliary power supply | AC/DC110/220V or AC380V, power comsumption 15VA | |
Rated working voltage of the motor | AC380V / 660V, 50Hz / 60Hz | |
Rated operating current of the motor | 1 (0.1A-5000A) | Adopt measurement module |
5 (0.1A-5000A) | ||
25(6.3A-25A) | ||
100(25A-100A) | ||
250(63A-250A) | Adopt outlay current tansformer and measurement module | |
800(250A-800A) | ||
Leakage | 50mA-1A or 3A-30A | Adopt measurement module and leakage current transformer |
Relay output contact capacity | Impedance load | AC250V; 6A; DC24V; 6A |
Master switching input and output | 4DI/4DO | |
Switching value module | 4DI/3DO | |
Temperature module | Type of external sensor: PT100、PT1000、Cu50、PTC、NTC | |
Channel of the sensor:3 channels | ||
Sensor’s corresponding measurement range: PT100/PT1000:-50°C~+500°C Cu50:-50°C~+150°C PTC/NTC:100Ω~30kΩ | ||
Analog module | 2-channel 4-20mA input and 2-channel 4-20mA output | |
Master communiction | RS485 Modbus_RTU | |
Communication module | double RS485 Modbus_RTU, Profibus_DP | |
Environment | Working temperature | -10ºC~55ºC |
Storage temperature | -25ºC~70ºC | |
Relative humidity | ≤95﹪No condensation, no corrosive gas | |
Altitude | ≤2000m | |
Pollution levels | Class 3 | |
Protection grade | Main body IP20, split display module IP45 (installed on the cabinet panel) | |
Installation category | Level III |
U, I, P, S, PF, F, EP, Leakage, PTC/NTC
Start control function
8 programmable DI
5 programmable DO
Modbus-RTU or Profibus-DP communication
1 DC4-20mA analog output
SOE
Anti-shaking function
Any IoT energy management system problem pls contact us, our experts will reply you within 24 hours.
Tel:
+86-18761599716
E-mail:
Address: