With the development of industrial technology, leakage current poses a great threat to the safety of industrial production. In order to improve the continuity and reliability of power supply, many important production sites have adopted IT power distribution systems (ungrounded power supply systems). Acrel designed the AIM-T series of industrial insulation monitoring and fault location products for this purpose.
Type | AIM-T500 | AIM-T300 | |
Accessory power supply | AC 85~265V; DC100~300V; 50/60Hz | AC 85~265V; DC100~300V; 50/60Hz | |
Power dissipation | < 8W | < 6W | |
System voltage | AC 0~690V; DC 0~800V; 40~460Hz | AC 0~480V; DC 0~480V; 40~460Hz | |
System application | IT system (online), Other system (offline) | IT system (online), Other system (offline) | |
Insulation monitoring | Measuring range | 1k~10MΩ | 1k~5MΩ |
Alarm range | 10k~10MΩ | 10k~5MΩ | |
Resistance accuracy | 1~10k,1k; 10k~10M, ±10% | 1~10k, 1k; 10k~5M, ±10% | |
system leakage capacitance | <500μF | <150μF | |
Response time (Ce=1μF) | <5s | <6s | |
Internal parameters | Measuring voltage | <50V | <20V |
Measuring current | <270μA | <170μA | |
Internal DC impedance | ≥180kΩ | ≥120kΩ | |
Relay output | Error, Alarm, Warning | Warning, Alarm | |
SOE | 20 records (fault type, fault value, fault time) | 20 records (fault type, fault value, fault time) | |
Alarm type | LCD, LED indicator | LCD, LED indicator | |
Communication | RS485, Modbus-RTU | RS485, Modbus-RTU | |
Impulse voltage / Pollution Level | 8kV/Ⅲ | 8kV/Ⅲ | |
EMC/ Radiation | IEC61326-2-4 | IEC61326-2-4 | |
Environment | Working temperature | -10 ~+65℃ | -10 ~+65℃ |
Storage temperature | -20~+70℃ | -20~+70℃ | |
Relative humidity | <95%, without condensation | <95%, without condensation | |
Altitude | ≤2500m | ≤2500m |
Industrial IT isolated power system is specially developed by ACREL for IT power distribution systems in industrial occasions such as mines, glass plants, electric furnaces and test equipment, ships, metallurgical plants, chemical plants, explosion-hazardous places, computer centers and emergency power supplies. The system has rich functions, including insulation resistance monitoring, insulation fault early warning, insulation fault alarm, event recording, parameter setting, communication networking, etc. When the system has a ground fault, it can alarm in time, and accurately locate the specific circuit where the fault occurs, so as to Remind the relevant personnel to troubleshoot the fault in time.
With the development of industrial science and technology, residual current poses a great threat to industrial production safety. In order to improve the continuity and reliability of power supply, many important production sites adopt IT distribution system (ungrounded system).
Mine, glass factory, electric furnace and test equipment, ship, metallurgical plant, chemical plant, explosion hazard site, computer center and emergency power supply.
Real-time monitoring of the ground insulation resistance of the IT system, and start the fault warning or alarm function when the resistance exceeds the limit.
Insulation monitoring and fault determination of power distribution system, providing safe, reliable and continuous power distribution.
Any IoT energy management system problem pls contact us, our experts will reply you within 24 hours.
Tel:
+86-18761599716
E-mail:
Address:
No.5 Dongmeng Road, Nanzha Street, Jiangyin City, Jiangsu Province, China.